Remote Power and Console Management |
Phone: (760) 930-0473
Toll-Free: (866) 790-3897
Fax: (760) 930-0550
View Cart
|
|
|
|
Back to Overview
|
NP-16 NP-1601DH NP-16A30 NP-16A20 NP-1601D
|
|
2-U, 16 Port Remote Power Switch System
|
|
Overview
|
|
Demo
netBooter™ NP-16 provides secured remote power source management operation and AC current monitoring (optional) via TCP/IP networks or local direct connection. Accessing the system is password protected at Administration level or user privilege levels. Network security includes user name and password (64-bit encrypted) authentication for Web access or sending emails. NP-16 offers the most versatile access control methods in the industry for easy, quick and reliable operations.
NP-1601D is integrated with AC current monitoring module.
NP-1601DH is equipped with IEC-320 C13 outlets and IEC-320 C14 inlets. 220VAC power supply.
NP-16A20 is equipped with one input AC power cord with NEMA L5-20P plug. NP-16A30 is installed with one input AC power cord with NEMA L5-30P plug. Both NP-16A20 and NP16-A30 are featured with AC current monitoring function. However, local current reading display and temperature sensing port are not equipped.
TS-0300 is an Environment Temperature Sensor Probe. It is an optional part for NP-1601D.
|
Applications:
- Controlling user equipment that requires operation AC power range from 100 VAC to 230 VAC, 50 to 60 Hz
- Control power sources for your equipment with your cellular phone or via emails when you are on the road or stuck in traffic.
- Scheduling AC outlet power cycling periodically or weekly scheduling.
|
|
|
Highlights
|
- 16 Independently Managed Power Outlets
- Redundant internal Power Supplies for More Reliable Operation
- AC Current Draw Monitoring (optional feature)
- Source IP Address Access Filtering/Blocking
- Telnet
- Web Browsing
- Email Interacting
- SNMP/Trap
- AutoPing & Reboot. Event Reporting via Emails.
- Modem Interface
- Local Control
- Manual Outlet Power Control Switch
- Standalone Calendar/Clock Timer for Each Power Outlet's Control
|
|
Features
|
- Standard 19” 2U chassis. 6” in depth.
- Handles large current equipment up to 30A @110VAC - 20A @220 VAC.
- 16 independently managed power outlets. Each power outlet is user name and password protected.
- Current Draw Monitoring (Optional) for user to view AC current draw from all power outlets. It includes settings for user defined alarm threshold, alarm methods (Emails, TRAP, data log) and alarm message sending intervals.
- 2 redundant internal power supplies for more reliable operation.
- One DB-9F(DCE) RS232 service port and one RJ45 Ethernet port.
- Source IP address Access Filtering/Blocking. Only one IP or a group of IP addresses can access the system.
- AutoPing and power reboot for each power outlet.
- Event timers for each power outlet so that an outlet is capable of executing recycling power with desired calendar date, real-time clock, and period and duty cycle.
- Telnet accessibility. Menu driven or command-in-line configuration setup.
- Embedded Web server enables user to easily change settings, view or alter system status.
- Integrated SNMP agent and Trap notification capability.
- POP3/SMTP for sending and receiving emails. Via Emails, users are able to send commands, such as power reboot.
- Dial-up modem connection via local serial port.
- Administration and User level name and password protection, including user name and password authentication for Web access or email sending.
- Calendar/Real-time clock timer for each power outlet's power control.
|
|
Specifications
|
|
| Item |
NP-16 |
NP-1601D |
NP-1601DH |
NP-16A20 |
NP-16A30 |
| Power Input: |
30 Amps Max |
30 Amps Max |
20 Amps Max |
20 Amps Max |
30 Amps Max |
| Voltage Range |
110VAC (Also support 220V) |
110VAC (Also support 220V) |
220VAC |
110VAC (Also support 220V) |
110VAC (Also support 220V) |
| Power Input Cord |
Two Power Cords |
Two Power Cords |
Two IEC-320 C14s |
One Power Cord |
One Power Cord |
| AC Output Outlets |
16 |
16 |
16 |
16 |
16 |
| Outlet Type |
NEMA 5-15 |
NEMA 5-15 |
IEC-320 C13 |
NEMA 5-15 |
NEMA 5-15 |
| Total Load (Combine all AC outlets) |
15+15 |
15+15 |
10+10 |
20 |
30 |
| AC Current Monitoring |
NO |
YES |
YES |
Yes |
Yes |
| Temperature Sensing |
NO |
Yes. (Sensor sold separately) |
Yes. (Sensor sold separately) |
NO |
NO |
| Console Interface
– Local Master Port |
1
RS232 Port. RJ-45 Connector. Data: 7 or 8 bits. Stop Bits: 1 or 2.
Parity: None, Odd or Even. Flow Control: None or RTS/CTS. Baud Rate:
2400 to 115200. |
| Network Interface |
10-Base T. RJ-45. |
| LED |
16 Power outlet On/Off status LEDs 2 Network LEDs. |
16 Power outlet On/Off status LEDs 2 Network LEDs. 2 digits AC readling . |
16 Power outlet On/Off status LEDs 2 Network LEDs. 2 digits AC readling. |
16 Power outlet On/Off status LEDs 2 Network LEDs. |
16 Power outlet On/Off status LEDs 2 Network LEDs. |
| Weight |
9 |
9 |
8 |
10 |
10 |
| Operational Temperature Environment |
-25C°
– 50C° |
| Humidity |
5-95%, non-condensing |
| Safety and EMI Compliance |
Yes.
TUV(US), UL-60950, FCC Class A |
|
|
Downloads
|
NP-16A30 Datasheet
NP-16A30 Startup Guide
NP-1601DH Datasheet NP-1601DH Startup Guide
NP-16A30 Datasheet NP-16A30 Startup Guide
NP-16A20 Datasheet NP-16A20 Startup Guide
NP-1601D Datasheet NP-1601D Startup Guide
NP netBooter Manual
Click here to view NP netBooter demo
|
| Accessories | C-RJ45-DB9F-4: RS-232 Serial RJ-45 to DB9 Female (DCE) Conversion Cable.